Coca-Cola is investigating a ransomware attack on its Fairlife dairy business, and production at Fairlife’s US facilities has been suspended while the company works out the full scope of the breach. The Canadian side of Fairlife was not affected and is staying open. Coca-Cola bought the rest of Fairlife in 2020, and in March it announced a $650 million investment to expand its facilities in Coopersville, Michigan.
OPC UA and its homegrown crypto
Plenty of utilities and factories run OPC UA, an open source protocol that’s often used in place of a VPN, and despite all of its cryptography it looks like it can be attacked in a number of ways.
Tom Tervoort, principal security specialist at Secura, gave a talk on OPC UA (Open Platform Communications Unified Architecture) at DEF CON 33. OPC UA first showed up in 2006, it works between different vendors, and it carries its own authentication and transport security, and that last bit is what drew Tervoort in, since the people who built it didn’t use TLS and wrote their own cryptographic protocol instead.
There are handshakes, private keys, session keys, encrypted messages, challenges and user logins in there, and Tervoort’s verdict on all of it was “redundant”. For example, Tervoort spotted that whether a message went from server to client or the other way round, it was formatted the same, with no metadata to say who it was for. So he worked up a proof of concept where a message signed for one purpose is reused for another, and the trick ends with two servers logging in to each other. Before any of that can work, though, the secure channel handshake has to be bypassed, and Tervoort found that because of how some configurations behave, an attacker can set up an HTTPS connection so that the protocol takes it for granted the traffic is encrypted and skips the handshake. He wrote a tool that does it automatically, but HTTPS versions of OPC UA are fairly new and he said almost nobody actually uses them. Then he went after the standard TCP version and found it supported PKCS #1, the encryption standard Swiss cryptographer Daniel Bleichenbacher broke in the late 1990s, and which some vendors still switch on by default.
Seven products turned out to be affected, and Tervoort expects many more are. Three CVEs from the research have been published (CVE-2024-42512, CVE-2024-42513 and CVE-2025-1468), and the OPC Foundation helped him reach the vendors. The fixes are a mix of software updates, features being switched off and configuration advisories, and for many (not all) setups disabling HTTPS and Basic128Rsa15 does the job. And if a company would rather keep going without a VPN, Tervoort’s advice was to use IP allowlisting, so only the connections it has approved can get through, especially if the server holds anything important.
Controllers left open to the internet
Attackers are using AI-generated exploit scripts to get into internet-exposed Siemens S7 Series programmable logic controllers at water, manufacturing, energy and other critical facilities, according to a joint alert from the NSA, CISA, the FBI, the Department of Energy and the EPA, which called it an active threat. The attackers take open source industrial automation libraries, specifically snap7, and use AI coding assistants to build custom tools that imitate OT monitoring software.
With those tools they can read and write the PLCs’ memory, config data and ladder logic over S7comm. The alert does not say who is behind the attacks. Iranian cyber operatives are suspected in recent attacks on PLCs at water and wastewater facilities in at least 12 states, including one in late July that disrupted more than 30 community water systems in Minnesota. Censys and ZoomEye, the internet-scanning services, are how they find their way in, turning up PLCs that are exposed, on outdated software or still on default passwords. If the PLCs are exposed to the internet or insufficiently segmented, the agencies said, attackers can exploit several known critical and high severity vulnerabilities in them. Benny Czarny, CEO and founder of Opswat, said AI makes it much easier to write and change scripts aimed at PLCs, but the bigger issue is still how exposed OT environments are.
Too much data, not enough connections
Manufacturers are dealing with more data than ever as they digitize their operations, and executives from Amgen, ArcelorMittal, Carpenter, Ford, GE Appliances and Magna talked about it at a May 6 event held by MIT’s Initiative for New Manufacturing. Ford is investing in automation and digitization, but Yung Fung, Ford’s managing director and general manager of advanced industrial technology and platforms, warned that more data is not always useful. Everything Ford is putting in, robots and AI systems included, gives off a signal, Fung said, and in a lot of cases there’s actually too much data, so what Ford wants to know is whether all those signals can be better connected.
At Carpenter Technology, a global alloys maker, the first chief digital officer arrived in 2021. Shakthi Logasundaram said data has always been treated as a byproduct of manufacturing when it should be treated as an asset, and he called it the number one challenge for Carpenter’s technical operations. The tough part, by his account, is the data from machines where there’s no standard and no control, because every machine is special. To get there, Carpenter put some technology spending on hold, and it’s working on an end-to-end data model of the organization. Some of that data isn’t even digital yet, since there are 240,000 pages of critical process data on paper, and Logasundaram reckons generative AI could help get them scanned in.
Amgen’s Arleen Paulino, SVP of global manufacturing, said she’ll think she has the right data and then find there’s another set somewhere else. Paulino said Amgen takes a control tower approach. People on the plant floor look after information about their own areas, a plant manager can see the whole site, and certain executives look at trends more broadly.
Over at GE Appliances, Bill Good, who runs supply chains, said the older plants have largely been retrofitted for full data tracking. He showed how he can follow production at company plants from an app on his phone, and said the most difficult problem is the one you can’t see.
Where office IT meets the plant floor
Coca-Cola said the Fairlife attack had not affected product quality or safety, and that it had notified law enforcement and was working with outside cybersecurity experts to restore its systems. Officials at the Food and Agriculture Information Sharing and Analysis Center said they were aware of the attack, the latest in a growing number against the industry, and that the sector has taken about 205 attacks so far in 2026, around 4.9% of all of them.
Scott Algeier, executive director of the Food and Ag-ISAC, said food and agriculture has been pulled into the same broad, opportunistic targeting that hits every other sector. Some adversaries may be going after the sector on purpose, he said, but they scan for exposed and vulnerable systems at machine speed and only work out the victim’s details after they’ve got in.
The Path Forward
The incidents described above point to a very limited set of jobs for plant operators:
- find out what’s exposed to the internet, since the PLC attacks started with scans on services such as Censys and ZoomEye which revealed a number of exposed controllers, obsolete software and default passwords;
- get the vendor fixes onto OPC UA systems, with HTTPS and Basic128Rsa15 turned off where they’re not required and IP allowlisting in place for the key servers that are running without a VPN;
- treat data as an asset and know who owns what data, as the manufacturers at the MIT event advocate, so that any anomalous activity is easier to spot.